Mobile Diesel Fired  Incinerator in container, 

supplied with the following specifications:

complete with constant ventilation fans for extraction, 

factory installed inside one 20ft ISO container complete with lighting, ventilation fan, fire security, 3 access doors, and a 1200 litre fuel tank complete with a piping. 

Fully containerised mobile  waste management solution for medical, animal, and industrial waste applications.

Installed in Container (ISO) : 20”

or its nearest equivalent model “

Tender Technical Specification

Destruction rate of 50kg/hr

Hot Hearth Principle

Refractory insulation:

a. Silicon carbide floor

b. Minimum 22mm insulation thickness

c. Brick lined Refractory insulation

d. Three layers of refractory insulation

e. Temperature Rating 1650 deg.C

f. 42% alumina fire bricks

Primary Chamber:

a. 120Kw Burner 

b. Dedicated independent fan system, damper controlled. 

c. Thermostatic Sensor 

d. Dimensions – 700mm x 700mm x g00mm

e. Square Chamber with curved floor for liquid centralization

Hot Hearth Chamber:

a. 120Kw Burner

b. Thermostatic Sensor 

c. Minimum Temperature of 1100 deg.C as per WHO guidelines. 

d. Two second retention time – Proven with CFD modeling.

Steel Construction:

a. constructed from 8mm & 1Omm steer plate 

b. Painted two pack paint system, red with black flashing

Control Panels:

a. Door dimensions 700mm x 700mm

b. Front mounted ash collection box.

Control Panels:

a. AiController

b. Plug and play 

c. Threezone monitoring of:

i)Primary chamber

              ii) Secondary chamber

              iii) Hot hearth

d. Digital display

e. Burner on-off indication lights 

f. Timer

Chimney:

a. Mild steel painted red

b. Refractory insulated with 50mm of insulation.

Unit Dimensions:

1840mm x 1 ‘1 50mm x 1950mm high.

Safety:

a. Burner door cut-off switches

b. Fire valve fitted to fuel system 

c. Maximum noise at 1m x g0 decibels 

d. Exterior temperature 70 deg.C Max