incineration Furnace for burning patalogical ( such as human tissue or blood ) as west
The weight of this west materials is 700 kg per month and we need an isolated furnace
Without fume and any harmful gas
. INCINERATOR SPECIFICATION
# Description Specification
1 Burning Capacity – 400 kg/time and should not be less than 300 kg/time. Maximum combustion time must be 6 times/day
2 Chimney external diameter – 300 to 400 mm
3 Fan power – Must not exceed 1.1kw
4 Voltage – 220V
5 Oil consumption – Must not exceed 14kg/h
6 Feeding door diagonal dimension (mm) – Not less than 500mm
7 Incineration Temp. (⁰C) – 800 or above
8 Emission
CO – Must not exceed 100 mg/m3
SO2 – Must not exceed 400 mg/m3
HF – (Hydrogen fluoride) Must not exceed 9.0 mg/m3
NO2 – Must not exceed 500 mg/m3
Smoke dust – Must not exceed 100 mg/m3
9 Height of the Incinerator – Not less than 10m above ground level
10 Manufacturer’s Warranty – Not less than 1 year
11 Electrical Connection – From nearest distribution box using 25mm2 electrical cable and all related connections and wiring